Voltage:120~690V
Rated Capacity:750~1250KVA
Rated Power:600~1000KW
●Comply with the most common standard in terms of GB755, EN ISO 12100, EN 12601, EN 60204-1
●Single or double bearings are available, options for all kinds of adaptors and coupling disc
●12-end reconnectable winding terminals to get different voltages
●Standard “H” insulation class
●Convenient installation and maintenance for rotated diodes and adaptor connected bolts
●Standard sealed maintenance-free bearings
●Air filter
●Droop CT
●PMG excitation system
●Winding RTD and bearing RTD
●IP23 or IP22 Protection
●Anti-condensation heater
●Winding protection thermistor and relay
●Double bearing transition joint
VOLTAGE | 4 POLES | 4 POLES | |||||
50Hz 1500rpm | 60Hz 1800rpm | ||||||
STAR-SERIES | 380 | 400 | 415 | 416 | 440 | 480 | |
STAR-PARALLEL | 190 | 200 | 208 | 208 | 220 | 240 | |
TRIANGLE-SERIES | 220 | 230 | 240 | 240 | 254 | 277 | |
WHI 6C | RATED CAPACITY (kVA) | 800 | 810 | 800 | 925 | 963 | 1000 |
RATED POWER (kW) | 640 | 640 | 640 | 740 | 770 | 800 | |
EFFICIENCY (%) | 94.1 | 94.4 | 94.5 | 94.3 | 94.4 | 94.6 | |
WHI 6D | RATED CAPACITY (kVA) | 912.5 | 944 | 912.5 | 1063 | 1075 | 1125 |
RATED POWER (kW) | 730 | 755 | 730 | 850 | 860 | 900 | |
EFFICIENCY (%) | 94.8 | 95.0 | 95.1 | 94.9 | 95.1 | 95.2 | |
WHI 6E | RATED CAPACITY (kVA) | 1025 | 1063 | 1025 | 1225 | 1275 | 1325 |
RATED POWER (kW) | 820 | 850 | 850 | 980 | 1020 | 1060 | |
EFFICIENCY (%) | 95.1 | 95.3 | 95.5 | 95.1 | 95.2 | 95.3 | |
WHI 6F | RATED CAPACITY (kVA) | 1138 | 1175 | 1138 | 1250 | 1313 | 1375 |
RATED POWER (kW) | 910 | 940 | 910 | 1000 | 1050 | 1100 | |
EFFICIENCY (%) | 95.1 | 95.2 | 95.5 | 95.1 | 95.2 | 95.5 | |
WHI 6G | RATED CAPACITY (kVA) | 1260 | 1315 | 1350 | 1525 | 1585 | 1630 |
RATED POWER (kW) | 1008 | 1052 | 1080 | 1220 | 1268 | 1304 | |
EFFICIENCY (%) | 94.8 | 94.6 | 94.5 | 95.0 | 94.9 | 94.8 |
The alternator has been designed for use in a maximum ambient temperature of 40℃ and altitude less than 1000 meters above sea level. The power factor is 0.8, and the level of raising temperature is H class (125℃)